Application
Our single phase and three phase pad-mounted distribution transformer is commonly used in various places including rural areas, remote regions and scattered villages to provide high quality power supply for daily lighting, agricultural production
and industrial plants. Aside from these, it is also suitable for the energy saving projects for railway and urban grid.
Standard
IEC60076,ANSI/IEEEC57.12.00, C57.12.20,C57.12.38, C57.12.90, BS171, SABS 780 etc
Advantage
1)Liquid-filled
2)dead front
3))separable,insulated,high-voltage connectors,radial or loop feed
4)standard or customer specific rating & configuration available,with a range of 10-167kVA
unlta-high efficiency transformers
extended additional warranty
Protection
Service condition
a) Both indoor or outdoor
b)Air temperature: Maximum temperature: +40℃; Minimum temperature:-25℃
c) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
d) Altitude above sea level: Maximum installation altitude: 2000m.
e) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
f) No frequent violent shake
Note: * Beyond those services condition should enquiry to manufacturer technical dept during order
Note: *The above parameter is only subject to our standard design, special requirement can be customized
Technical parameters
1.As per IEEE standard C57.12.38-2009(type 2 arrangement units only)
& CSA standard CAN/CSA-C227.3-06(R2011)
2.kVA rating:10-167
3.Primary Voltage:2400-19920
4.HV BIL:60,75,95,125,150KV
5.Secondary Voltage:120-600V
6.ONAN,60HZ
7.Average temperature rise should not exceed 65℃